MODSUR
SURGE GENERATOR RANGE
Electricity supply or distribution companies often find that buried power cables become faulty due to ageing or damage. Because energy cables are normally not supplied in lengths much longer than 300m, inevitably many joints are installed and buried. They are often the cause for cable faults which render the cable useless until repaired and put back into service. Surge generators are used in conjunction with pre-location and pinpoint location equipment to precisely locate the position of cable faults.
MODSUR Surge Generator Range
As cable maintenance becomes ever more challenging, test engineers require more sophisticated methods to easily and accurately pinpoint the position of cable faults. As standard, the Modsur surge generator comes equipped with an ICE signal output to connect to any cable fault location TDR for fault pre-location. The Modsur forms part of our flexible, configurable Modsys fault location system offering endless possibilities. By coupling the Modsur to our latest PCA101 and Modarc systems, you can accurately pre-locate fault positions using the well known ICE method. Our MCLS (Mains Condition Lockout System) ensures proper and safe earthing connection. The MCLS system also ensures the quality of the mains power source.
Output Voltage
Modsur22-550 0-22kV, 550 Joules
Modsur22-1100 0-22kV, 1100 Joules
Modsur32-1100 0-32kV, 1100 Joules
Modsur32-2200 0-32kV, 2200 Joules
MCLS
(Mains Condition Lockout System)
Checks Mains Polarity
Checks Mains Hi
Checks Mains Low
Checks Earthing Integrity
Pulse Rate
Every 4 Seconds
Single Shot
DC Test
Modsur22 – 0-22kV@20mA Current Limited
Modsur32 – 0-32kV@20mA Current Limited
Burning Function
100mA @ Low voltage range selection
400mA @ High voltage range selection
(Limited to short period only)
Capacitor
Steel Enclosed Oil Filled(Non PCB)
Porcelain Insulators
Enclosure
308 Stainless Steel IP21
HV Transformer
Dry Type Temperature Protected
4 Individual Secondary Coils
Test Method Options
ICE Coupler: Built-In
Dimensions
500mm H x 810mm D x 460mm W
Weight
Modsur22 – 550, 100kg
Modsur22 – 1100, 100kg
Modsur32 – 1100, 118kg
Modsur32 – 2200, 118kg
Mobility
Trolley, Trailer or Van Mount
Test Environment
Temperature indoor and outdoor: 10ºC to
+ 45ºC.
Humidity: < 85%
Supply Voltage
230V 50/60Hz, 16A
Standard Accessories
5m High voltage test lead
1.5m Mains lead
5m Earth Lead